A house or flat with its own heating circuit needs flushing when deposits have built up in the heating water and some radiators no longer warm up. The price depends on the number of radiators, how dirty the water is and whether a flushing agent is used. For that reason this job has no single starting price.
Valve positions noted before the flush
Kamco, a maker of flushing machines, advises in its Clearflow instructions that every radiator valve setting is recorded before flushing. That means the number of turns each valve is open, counted from closed. After the work the system can then easily be set as it was, without balancing it again.
Balancing is the adjustment after which the farthest and nearest radiators each receive their share of heat. If someone has done it in the past, that work is valuable and should not be lost in a flush. The record can be simple: room, radiator, valve and number of turns.
| Room | Radiator | Valve | Turns from closed |
|---|---|---|---|
| Bedroom | by the window | thermostatic | write the number |
| Kitchen | on the wall | return | write the number |
This is only a sample record. Count the turns by carefully closing the valve fully and then opening it back to where it was. If the valve has a presetting mark, go by that instead.
Presettings opened all the way
The manufacturer Purmo states for its panel radiators that if the pipework needs flushing, the presettings of the radiator valves are opened to maximum. They are adjusted only after the flush. A fully open valve lets more water through, so deposits are washed out of the radiator more easily.
The two instructions complement each other. First the position of every valve is noted, then the presettings are opened, the system is flushed and the valves are returned to the recorded positions.
Kamco Clearflow instructions and the Purmo panel radiator instructions, checked on 25 November 2026. These are manufacturers' guidance; for a particular system, see the documents for its radiators and valves.
The worst radiator goes first
Kamco gives one more rule of order: if the first inspection finds cold or partly clogged radiators, flushing radiators one by one starts with the worst. The scope of work and the price are affected by:
- Number of radiators
- the more there are on the circuit, the longer the work takes.
- State of the heating water
- dark, cloudy water with particles needs more flushing than nearly clean water.
- Flushing agent
- if one is used, it is a separate material and affects the price.
Flow direction, a reading and what stays in the system
In the Kamco flushing procedure the thermostatic valves are opened fully, their heads are removed and each valve pin is checked for free movement. Each radiator is then flushed on its own, reversing the flow regularly, until the cold spots disappear and the temperature is even across the whole radiator.
Kamco advises judging when to stop by a reading rather than by eye. The total dissolved solids (TDS) of the outflowing water are compared with tap water. Flushing continues until the two readings differ by no more than 5-10%. After that the system is full of clean water. Kamco states that a good-quality corrosion inhibitor has to be added to it so that new deposits do not form.
The radiator material must be known before the work. Kamco does not allow its acidic agent POWERFLUSH FX2 in systems with aluminium radiators or heat exchangers; an acid-free agent is meant for those. A specialist applies the flushing agent and inhibitor following the manufacturer’s directions.
Kamco Clearflow instructions, viewed on 25 November 2026. This is the procedure of a flushing equipment manufacturer, not a Latvian standard.
A block of flats and a house with its own boiler
In a block of flats on district heating the heating system is shared. Its flushing usually has to be discussed with the building manager, unless the house documents say otherwise. In a private house with its own boiler and heating circuit the owner decides alone, and the valve record stays with the owner for next time too.